Professional Equipment for Water Treatment
Call Us:
801-265-1000
The detector is designed to trigger alarms when ozone exceeds safety thresholds, with a warning level set at 0.1 ppm and a system shutdown/interlock trigger at 0.3 ppm, ensuring rapid protective action. It can be powered from a 10–40 V DC supply (50–60 Hz compatibility) or battery power, and is suitable for operation in environments from –20 °C to +55 °C with high relative humidity (up to 99 % RH). The rugged housing provides IP65 dust and moisture protection, making it suitable for industrial installations and harsh conditions.
Technical Specifications:
Measurement Range: 0–1 ppm O₃
Accuracy / Linearity: < 0.5 % of full scale
Alarm Threshold: 0.1 ppm
Shutdown/Interlock Threshold: 0.3 ppm
Output: 4–20 mA analogue for remote PLC/SCADA integration
Power Supply: 10–40 V DC, 50–60 Hz or battery
Operating Temperature: –20 °C to +55 °C
Humidity Range: 0–99 % RH
Ingress Protection: IP65 (dust and moisture resistance)
Sensor Technology: Electrochemical cell for ozone detection
Free support line!
Orders Support!
Working Days/Hours!